Product Data Sheet    

PT7FSDGYC

With Hubbell HBL5252 series (15A) specification grade receptacle & two low-voltage knockouts. Equipped with a cast aluminum carpet flange and a thermoplastic (ABS) duplex flap cover.
These flush poke-throughs include a prewired specification grade duplex receptacle and have provisions for voice/data cabling (isolated ground units are also available). Versions are offered in brushed brass or in four designer colors. These poke-throughs can be ordered as a one-piece unit (flush service fitting and through-floor fitting combined) or as two-piece units (flush service fitting and through-floor fitting ordered separately).

Hubbell Wiring Device-Kellems Product Specifications
 Poke-Through Style  
 Type  2 Outlet Flush
 Item  Complete Unit
 Core Hole Size  3"
 Flush Service Type  Duplex Receptacle with Low Voltage Option
 Amperage  15
 Color  
 Fire Rating  For use in 1, 1 1/2, 2, 3, or 4 hour rated unprotected reinforced concrete floors or in 1, 2, or 3 hour rated floors employing steel floor units and concrete topping (D900 Series design).
 Floor Thickness Range  2 1/4" (over metal deck) to 7" (57.2mm to 177.8mm).
 UL Installation Spacing  Minimum of 2 feet O.C. and not more than one unit per each 65 sq. ft. of floor area in each span.
 Cored Hole  3" (76.2) diameter
 Power Conductors  #12 AWG THHN stranded copper
 Device Cover and Flaps Material  Thermoplastic
 Carpet Flanges Material  Painted Cast Aluminum
 Power Conduit Tubes Material  3/4" EMT
 Junction Box  13.0 cubic inches; eight 3/4" knock outs
 Outlet Box UL Listing  E31999
 Fire Resistance UL Listing  R8429
 Style  Flush

Product Information

• Independent, spring-loaded lift covers are self-closing to protect receptacles when they are not in use. . . will not stick open like sliding covers.

• Flush die-cast aluminum carpet flange and thermoplastic lift cover or opt for all brass.

• ¾" pre-wired conduit contains and isolates power conductors.

• Two low-voltage openings for up to one 25 pair telephone cable per opening. . . will accept low-profile voice/data jack.

• Units come standard with a pre-wired HBL5352 or IG5362 series receptacle (15A, HBL5252 series for Canadian units).

• Stationary fire barrier expands during fire conditions to provide an upper fire seal.

• Adjustable fire barrier accommodates floor thickness from 2 ¼" to 7" (57.2 to 177.8) - Seals bottom of the core drilled hole.

• Integral junction box incorporates seven ¾" knockouts.


Applications Data

Mounted in core drilled 3" (76.2) diameter hole through the concrete floor.

Floor thickness range: 2 1/4" to 7" (57.2 to 177.8).

UL Listed for fire resistance in 1-4 hour rated floors.





 

Hubbell Wiring Device-Kellems